DocumentCode :
813528
Title :
Round-robin artificial contamination test on high voltage DC insulators
Author :
Naito, K. ; Schneider, H.M.
Volume :
10
Issue :
3
fYear :
1995
fDate :
7/1/1995 12:00:00 AM
Firstpage :
1438
Lastpage :
1442
Abstract :
This paper summarizes the results of a worldwide round-robin test of high voltage DC (HVDC) insulators, which was carried out in six laboratories aiming at standardization of the method for artificial contamination tests on HVDC insulators. Flashover characteristics of three kinds, of specimens mere evaluated by the clean fog and the salt fog procedures. Sufficient information is now available to allow the preparation of provisional international specifications for artificial contamination testing of HVDC insulators
Keywords :
HVDC power transmission; electric breakdown; flashover; insulator contamination; insulator testing; standardisation; standards; HVDC insulators; artificial contamination test; breakdown; clean fog procedure; flashover characteristics; international specifications; laboratories; round-robin test; salt fog procedure; standardization; Aggregates; Conductors; Electrodes; Flashover; Insulation; Insulator testing; Pollution; Surface contamination; Temperature; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.400927
Filename :
400927
Link To Document :
بازگشت