Abstract :
This paper addresses the use of multiple active power line conditioners (APLCs) for holding harmonic voltages and voltage distortion in a power system within IEEE-519 guidelines while minimizing APLC injection current or several other alternative network functions. The authors propose a sequential one-APLC placement procedure for computing initial current injections and locations of APLCs, followed by the nonlinear optimizing program GRG2 to improve the solution further. They illustrate the usefulness of the procedure with a distribution system example
Keywords :
IEEE standards; control system CAD; control system analysis computing; digital simulation; distribution networks; harmonic distortion; power system CAD; power system analysis computing; power system control; power system harmonics; software packages; GRG2; HARMFLO package; IEEE-519 guidelines; computer simulation; distribution system; harmonic voltage; initial current injections; injection current; multiple active power line conditioners; nonlinear optimizing program; power system; sequential one-APLC placement procedure; voltage distortion; Control systems; Harmonic distortion; Power system harmonics; Power system modeling; Senior members; Student members; Telephony; Total harmonic distortion; Transfer functions; Voltage control;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.400955
Filename :
400955
Link To Document :
بازگشت