DocumentCode :
815371
Title :
Lessons learned through commissioning and analyzing data from transformer differential installations
Author :
Costello, D.
Author_Institution :
Schweitzer Eng. Labs., Pullman, WA
Volume :
44
Issue :
4
fYear :
2008
Firstpage :
979
Lastpage :
1003
Abstract :
Ensuring correct setting and installation of a transformer differential relay is critical. A transformer differential relay must detect internal faults, damaging overloads, and through-fault currents while remaining secure against misoperation. The ability to use wye-connected current transformers with microprocessor-based relays has simplified installations, and these relays provide better commissioning tools than those available with traditional relays. However, installations and commissioning remain complicated. Installation and settings errors continue to be widespread, implying a need for more rigorous commissioning tests. Even with greater commissioning effort, occasional wiring problems develop over time, and these can best be resolved through analysis of relay event-report data. In the interest of reducing transformer differential misoperations, we share in this technical paper practical lessons we have learned through experience with commissioning and relay event-report analysis.
Keywords :
current transformers; data analysis; differential transformers; fault currents; fault diagnosis; relay protection; internal faults detection; microprocessor-based relays; through-fault currents; transformer differential installations; wye-connected current transformers; Circuit faults; Current transformers; Data analysis; Displays; Filtering; Protection; Protective relaying; Relays; Testing; Wiring; Commissioning; differential element; event analysis; event reports; protective relay; transformer differential relay;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.2008.926206
Filename :
4578781