DocumentCode
81851
Title
Thermal-Electric Rating Method for Mass-Impregnated Paper-Insulated HVDC Cable Circuits
Author
Huang, Z.Y. ; Pilgrim, J.A. ; Lewin, P.L. ; Swingler, S.G. ; Tzemis, G.
Author_Institution
Tony Davies High Voltage Lab., Univ. of Southampton, Southampton, UK
Volume
30
Issue
1
fYear
2015
fDate
Feb. 2015
Firstpage
437
Lastpage
444
Abstract
Compared to conventional ac cables, the current rating of HVDC cable circuits is more complicated because the permissible current is not only limited by the operating temperature, but also by the electrical stress within the insulation. Therefore the IEC60287 current rating standard is considered insufficient for some HVDC applications because it fails to include the stress limitation. This paper presents an analytical methodology to calculate an electrical stress-limited rating for HVDC cables, which considers the maximum dielectric stress as the current limiting factor. This paper represents the first part of a project which has comprehensively reviewed cable rating calculations for mass impregnated HVDC cable systems.
Keywords
HVDC power transmission; IEC standards; cable insulation; current limiters; paper; stress analysis; IEC60287 current rating standard; cable insulation; cable rating calculation; current limiting factor; electrical stress; electrical stress-limited rating; high voltage direct current; mass-impregnated paper-insulated HVDC cable circuit; maximum dielectric stress; permissible current; thermal-electric rating method; Cable insulation; Conductivity; Conductors; Dielectrics; HVDC transmission; Stress; Electric breakdown; HVDC transmission; power cable insulation; underwater cables;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2014.2359772
Filename
6908003
Link To Document