• DocumentCode
    82123
  • Title

    Improvement on Stability and Islanding Detection Performances by Advanced Inverter Control of DG

  • Author

    Soo Hyoung Lee ; Jung-Wook Park

  • Author_Institution
    Sch. of Electr. & Comput. Eng., Georgia Inst. of Technol., Atlanta, GA, USA
  • Volume
    28
  • Issue
    4
  • fYear
    2013
  • fDate
    Nov. 2013
  • Firstpage
    3954
  • Lastpage
    3963
  • Abstract
    The islanding detection is one of the most important issues for grid-connection of the distributed generation (DG) systems. Several recent researches have developed two types of islanding detection methods (IDMs) with high-performance. One is the power and voltage (P-V) characteristic of load based IDM, and the other is the inverter´s switching frequency based IDM. Although the above IDMs have no non-detection zone (NDZ) theoretically, their usefulness mainly depends on the control performance of the inverter in practice. In other words, the inverter must achieve the decoupled real and reactive control and successful operation of phase-locked loop (PLL). To deal with these problems, this paper describes the design of inverter controller to improve both system stability and islanding detection performance with the NDZ. The proposed controller uses the magnitude and phase of measured voltage directly instead of using the direct and quadrature axes voltages and currents. Additionally, it does not need an instant phase of point of common coupling (PCC) voltage, which is required in the conventional controller, and therefore makes it possible for the PLL independent control. Several case studies are carried out to verify that the proposed controller has better performance than the conventional controller.
  • Keywords
    control system synthesis; distributed power generation; invertors; phase locked loops; power generation control; power grids; DG system; NDZ; P-V characteristic; PCC voltage; PLL independent control; advanced inverter control; distributed generation systems; inverter controller design; inverter switching frequency based IDM; islanding detection methods; islanding detection performances; load based IDM; nondetection zone; phase-locked loop; point of common coupling; power-voltage characteristic; quadrature axes voltages; reactive control; system stability; Distributed generation (DG); inverter control algorithm; islanding detection; phase-locked loop (PLL) independent control; stability;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2013.2262716
  • Filename
    6522164