DocumentCode
821514
Title
Fast extraction of positive-sequence current from harmonically corrupted three-phase currents for TCR compensator control systems
Author
Ho, P.T. ; Tso, S.K.
Author_Institution
Dept. of Electr. & Electron. Eng., Hong Kong Univ., Hong Kong
Volume
37
Issue
1
fYear
1990
Firstpage
82
Lastpage
85
Abstract
The authors discuss a practical scheme for extracting the magnitude of the positive-sequence component from harmonically corrupted three-phase currents found in modern energy systems. The scheme is cost-effective, fast, and simple in design, with the novel combination of software processing and digital and analog circuits. The scheme has been successfully applied to a microprocessor-based thyristor-controlled reactor (TCR) control system and is suitable for similar real-time applications that already include one or more processing units. It is demonstrated that the scheme is adequately fast for the TCR control system because the extraction delay is typically less than half a cycle. The scheme is especially suitable for microprocessor-based control systems because the averaging function can be advantageously performed by software.<>
Keywords
compensation; harmonics; microcomputer applications; power system computer control; reactive power; thyristor applications; control system; extraction delay; harmonically corrupted three-phase currents; microprocessors; positive-sequence component; power system computer control; reactive power compensation; software processing; thyristor-controlled reactor;
fLanguage
English
Journal_Title
Industrial Electronics, IEEE Transactions on
Publisher
ieee
ISSN
0278-0046
Type
jour
DOI
10.1109/41.45847
Filename
45847
Link To Document