DocumentCode :
822061
Title :
Fire protection wrapped cable tray ampacity
Author :
Save, Phil ; Engmann, Gary
Author_Institution :
Southern California Edison Co., Los Angeles, CA, USA
Volume :
4
Issue :
4
fYear :
1989
fDate :
12/1/1989 12:00:00 AM
Firstpage :
575
Lastpage :
584
Abstract :
A method is presented for calculation of ampacity of cable in fire protection wrapped cable trays. A brief description of the model is presented. The iterative technique used for solution of the model´s simultaneous transcendental equations is presented with a description of the computer program. Cable derating for several typical installations is given and a graph is developed for use with ICEA P-55-440. To use the graph, the only data needed are the wrap thickness-to-conductivity ratio and emissivity. Ampacity derating derived from the model is also compared with published test results for two different fire wrap systems
Keywords :
fires; flameproofing; power cables; power engineering computing; ICEA P-55-440; computer program; emissivity; fire protection wrapped cable trays; power cables; simultaneous transcendental equations; wrap thickness-to-conductivity ratio; Conductors; Equations; Fires; Heat transfer; Power cables; Power system modeling; Power system protection; System testing; Temperature; Thermal resistance;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.41716
Filename :
41716
Link To Document :
بازگشت