• DocumentCode
    822061
  • Title

    Fire protection wrapped cable tray ampacity

  • Author

    Save, Phil ; Engmann, Gary

  • Author_Institution
    Southern California Edison Co., Los Angeles, CA, USA
  • Volume
    4
  • Issue
    4
  • fYear
    1989
  • fDate
    12/1/1989 12:00:00 AM
  • Firstpage
    575
  • Lastpage
    584
  • Abstract
    A method is presented for calculation of ampacity of cable in fire protection wrapped cable trays. A brief description of the model is presented. The iterative technique used for solution of the model´s simultaneous transcendental equations is presented with a description of the computer program. Cable derating for several typical installations is given and a graph is developed for use with ICEA P-55-440. To use the graph, the only data needed are the wrap thickness-to-conductivity ratio and emissivity. Ampacity derating derived from the model is also compared with published test results for two different fire wrap systems
  • Keywords
    fires; flameproofing; power cables; power engineering computing; ICEA P-55-440; computer program; emissivity; fire protection wrapped cable trays; power cables; simultaneous transcendental equations; wrap thickness-to-conductivity ratio; Conductors; Equations; Fires; Heat transfer; Power cables; Power system modeling; Power system protection; System testing; Temperature; Thermal resistance;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.41716
  • Filename
    41716