DocumentCode
822061
Title
Fire protection wrapped cable tray ampacity
Author
Save, Phil ; Engmann, Gary
Author_Institution
Southern California Edison Co., Los Angeles, CA, USA
Volume
4
Issue
4
fYear
1989
fDate
12/1/1989 12:00:00 AM
Firstpage
575
Lastpage
584
Abstract
A method is presented for calculation of ampacity of cable in fire protection wrapped cable trays. A brief description of the model is presented. The iterative technique used for solution of the model´s simultaneous transcendental equations is presented with a description of the computer program. Cable derating for several typical installations is given and a graph is developed for use with ICEA P-55-440. To use the graph, the only data needed are the wrap thickness-to-conductivity ratio and emissivity. Ampacity derating derived from the model is also compared with published test results for two different fire wrap systems
Keywords
fires; flameproofing; power cables; power engineering computing; ICEA P-55-440; computer program; emissivity; fire protection wrapped cable trays; power cables; simultaneous transcendental equations; wrap thickness-to-conductivity ratio; Conductors; Equations; Fires; Heat transfer; Power cables; Power system modeling; Power system protection; System testing; Temperature; Thermal resistance;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/60.41716
Filename
41716
Link To Document