DocumentCode :
822183
Title :
Dynamic analysis of generation control performance standards
Author :
Sasaki, Tetsuo ; Enomoto, Kazuhiro
Author_Institution :
Kansai Electr. Power Co. Inc., Osaka, Japan
Volume :
17
Issue :
3
fYear :
2002
fDate :
8/1/2002 12:00:00 AM
Firstpage :
806
Lastpage :
811
Abstract :
This paper presents an evaluation of the North American Electric Reliability Council´s (NERC) new control performance standards, as they might be applied to the Western Japanese 60-Hz system. Dynamic simulation of the system frequency response, including the effects of primary and secondary frequency control, power plant response, and load fluctuation characteristic were performed using a load flow program during normal system operation. Parameter sensitivities have been studied for some of the pertinent control parameters influencing the generation control performance, including power plant and automatic generation control (AGC) response parameters and amounts of generation under control for governor and AGC.
Keywords :
control system analysis computing; frequency control; frequency response; power generation control; power generation reliability; power system analysis computing; 60 Hz; Japan; NERC; North American Electric Reliability Council; frequency response; generation control performance; generation control performance standards; load flow program; load fluctuation characteristic; parameter sensitivities; power plant response; primary frequency control; secondary frequency control; system frequency response; Automatic generation control; Control systems; Fluctuations; Frequency control; Performance analysis; Power generation; Power system control; Power system modeling; Power system reliability; Power systems;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2002.800946
Filename :
1033729
Link To Document :
بازگشت