DocumentCode :
826189
Title :
Ground resistance of the foot in substation yards
Author :
Thapar, Baldev ; Gerez, Victor ; Emmanuel, Prince
Author_Institution :
Montana State Univ., Bozeman, MT, USA
Volume :
8
Issue :
1
fYear :
1993
fDate :
1/1/1993 12:00:00 AM
Firstpage :
1
Lastpage :
6
Abstract :
Equations and graphs given in IEEE Std 80 to determine ground resistance are not accurate and give conservative results. More accurate equations and graphs for determining the ground resistance of the human foot in a substation with a thin surface layer of gravel are given. An analysis has been made for models of the foot. In one model the foot is represented by an equivalent circular plate and in the other by an equivalent rectangular plate. Results obtained with these two models and with the IEEE Std 80 method are compared
Keywords :
earthing; electric resistance; standards; substations; IEEE Std 80; equivalent circular plate; equivalent rectangular plate; gravel surface layer; ground resistance; human foot; substation yards; Conductivity; Equations; Foot; Grounding; Immune system; Safety; Soil; Substations; Surface resistance; Voltage;