Title :
Experimental verification of three-phase four-wire current-regulated PWM converter
Author :
Lin, B.-R. ; Yang, T.-Y.
Author_Institution :
Dept. of Electr. Eng., Univ. of Sci. & Technol., Yunlin, Taiwan
fDate :
5/6/2005 12:00:00 AM
Abstract :
A bidirectional power flow, three-phase AC/DC converter is presented to implement power factor correction, regulate the DC-bus voltage and draw balanced and sinusoidal line currents from AC source. Four switches are adopted in each converter leg to generate a three-level PWM waveform on the AC terminal to neutral-point voltages. Compared with conventional three-phase three-level converters, the proposed converter has a simpler circuit configuration and fewer power semiconductors. The classical proportional-integral voltage controller and carrier-based current controller are adopted in the outer loop and inner loop to implement DC-bus voltage regulation and current-command tracking, respectively. Simulation and experimental results verify the validity and effectiveness of the control scheme.
Keywords :
AC-DC power convertors; PI control; PWM power convertors; electric current control; power factor correction; rectifying circuits; voltage control; DC-bus voltage regulation; bidirectional power flow AC/DC converter; carrier-based current controller; current-command tracking; power factor correction; proportional-integral voltage controller; three-level converters; three-phase four-wire current-regulated PWM converter;
Journal_Title :
Electric Power Applications, IEE Proceedings -
DOI :
10.1049/ip-epa:20045220