    Investigations of multiple reignition phenomena and protection scheme of shunt reactor current interruption in GIS substations

  • Author

    Okabe, S. ; Kosakada, M. ; Toda, H. ; Suzuki, K. ; Ishikawa, M.

  • Author_Institution
    Tokyo Electr. Power Co., Japan
  • Volume
    8
  • Issue
    1
  • fYear
    1993
  • fDate
    1/1/1993 12:00:00 AM
  • Firstpage
    197
  • Lastpage
    202
  • Abstract
    Field measurement and computer analysis concerning 150 MVA shunt reactor current interruptions at a 275 kV gas insulated substation (GIS) were carried out to verify that high-frequency current interruptions can be caused by certain system structures on the circuit breaker power supply side. A shunt reactor current-interrupting test was conducted with phase angle control, which is considered to be the best method for preventing multiple reignitions, using short-circuit test facilities. The possibility of stable reignition-free interruption was confirmed, even when the longest arcing time is preset
  • Keywords
    circuit breakers; circuit-breaking arcs; gaseous insulation; substations; switchgear testing; 150 MVA; 275 kV; GIS; arcing; circuit breaker; gas insulated substation; multiple reignition; phase angle control; power supply; protection; short-circuit test; shunt reactor current interruption; substations; Circuit analysis computing; Circuit breakers; Current measurement; Gas insulation; Geographic Information Systems; Inductors; Power measurement; Power system protection; Shunt (electrical); Substation protection;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.180337
  • Filename
    180337