DocumentCode
826714
Title
A survey of harmonic voltages and currents at the customer´s bus
Author
Emanuel, Alexander E. ; Orr, John A. ; Cyganski, David ; Gulachenski, Edward M.
Author_Institution
Worcester Polytech. Inst., MA, USA
Volume
8
Issue
1
fYear
1993
fDate
1/1/1993 12:00:00 AM
Firstpage
411
Lastpage
421
Abstract
Seven day-measurements of harmonic current and voltage made at the main buses of industrial, commercial, and residential customers are reported. The results are for a large residential load, an accounting operations building, a welded pipes plant, a passing and machining plant, a large supermarket, and a retail store. The results are representative of low-voltage buses in the northeast US. At all the locations it was found that 99% of the time the voltage total harmonic distortion was much smaller than 5% limit recommended by IEEE Std 519. The data provide the initial core of documentation for future reference and follow-up of the trends in harmonic levels at end users
Keywords
busbars; harmonics; power system measurement; IEEE Std 519; LV buses; accounting operations building; commercial customers; harmonic currents; harmonic voltages; industrial customers; large residential load; machining plant; passing plant; residential customers; retail store; supermarket; voltage total harmonic distortion; welded pipes plant; Arithmetic; Documentation; Histograms; Low voltage; Monitoring; Phase transformers; Power system harmonics; Reactive power; Statistical distributions; Stochastic processes;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.180363
Filename
180363
Link To Document