• DocumentCode
    826714
  • Title

    A survey of harmonic voltages and currents at the customer´s bus

  • Author

    Emanuel, Alexander E. ; Orr, John A. ; Cyganski, David ; Gulachenski, Edward M.

  • Author_Institution
    Worcester Polytech. Inst., MA, USA
  • Volume
    8
  • Issue
    1
  • fYear
    1993
  • fDate
    1/1/1993 12:00:00 AM
  • Firstpage
    411
  • Lastpage
    421
  • Abstract
    Seven day-measurements of harmonic current and voltage made at the main buses of industrial, commercial, and residential customers are reported. The results are for a large residential load, an accounting operations building, a welded pipes plant, a passing and machining plant, a large supermarket, and a retail store. The results are representative of low-voltage buses in the northeast US. At all the locations it was found that 99% of the time the voltage total harmonic distortion was much smaller than 5% limit recommended by IEEE Std 519. The data provide the initial core of documentation for future reference and follow-up of the trends in harmonic levels at end users
  • Keywords
    busbars; harmonics; power system measurement; IEEE Std 519; LV buses; accounting operations building; commercial customers; harmonic currents; harmonic voltages; industrial customers; large residential load; machining plant; passing plant; residential customers; retail store; supermarket; voltage total harmonic distortion; welded pipes plant; Arithmetic; Documentation; Histograms; Low voltage; Monitoring; Phase transformers; Power system harmonics; Reactive power; Statistical distributions; Stochastic processes;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.180363
  • Filename
    180363