DocumentCode :
829131
Title :
New method for measurement of the resistive leakage currents of metal-oxide surge arresters in service
Author :
Lundquist, J. ; Stenström, L. ; Schei, A. ; Hansen, B.
Author_Institution :
Asea Brown Boveri HV Switchgear, Ludvika, Sweden
Volume :
5
Issue :
4
fYear :
1990
fDate :
10/1/1990 12:00:00 AM
Firstpage :
1811
Lastpage :
1822
Abstract :
Various methods of determining the condition of zinc oxide (ZnO) surge arresters by means of measuring their leakage current are discussed. A method that minimizes the influence of harmonics in the system voltage when performing a harmonic analysis of the arrester leakage current presented. The presence of harmonics in the voltage has presented a great problem to earlier methods based on harmonic analysis, since these harmonics may interfere with the harmonics generated by the nonlinear resistance of the arrester. The favorable effect of the method presented is achieved by introducing a field probe which allows a compensation for the harmonics in the voltage. The main advantage of the new method is the low sensitivity to harmonics in the system voltage
Keywords :
electric current measurement; harmonic analysis; surge protection; zinc compounds; ZnO surge arresters; field probe; harmonic analysis; leakage current measurement; nonlinear resistance; resistive leakage currents; Arresters; Capacitance; Current measurement; Harmonic analysis; Leakage current; Power system harmonics; Surge protection; Varistors; Voltage; Zinc oxide;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.103677