Fourteen Years of Data on the Operation of One Hundred Ungrounded 240-and 480-Volt Industrial Distribution Systems
Author
Gienger, John A.
Author_Institution
Eastman Kodak Company
Issue
2
fYear
1966
fDate
3/1/1966 12:00:00 AM
Firstpage
147
Lastpage
150
Abstract
A discussion is given of the data found over a fourteen-year period of 240-and 480-volt ungrounded industrial distribution system operation at Kodak Park Works, Eastman Kodak Company. An advantage of the ungrounded system over the grounded system is the higher degree of reliability that is attainable. One drawback of the system is the problem of locating a ground when it occurs. Practical and successful tracing of grounds with power on are possible and, when combined with systematic detecting and clearing, the ungrounded system may offer further advantages over the grounded system.
Keywords
Chemical industry; Chemical processes; Circuits; Coils; Conductors; Industrial accidents; Industrial power systems; Manufacturing industries; Manufacturing processes; Power system reliability;
fLanguage
English
Journal_Title
Industry and General Applications, IEEE Transactions on