• DocumentCode
    829745
  • Title

    Fourteen Years of Data on the Operation of One Hundred Ungrounded 240-and 480-Volt Industrial Distribution Systems

  • Author

    Gienger, John A.

  • Author_Institution
    Eastman Kodak Company
  • Issue
    2
  • fYear
    1966
  • fDate
    3/1/1966 12:00:00 AM
  • Firstpage
    147
  • Lastpage
    150
  • Abstract
    A discussion is given of the data found over a fourteen-year period of 240-and 480-volt ungrounded industrial distribution system operation at Kodak Park Works, Eastman Kodak Company. An advantage of the ungrounded system over the grounded system is the higher degree of reliability that is attainable. One drawback of the system is the problem of locating a ground when it occurs. Practical and successful tracing of grounds with power on are possible and, when combined with systematic detecting and clearing, the ungrounded system may offer further advantages over the grounded system.
  • Keywords
    Chemical industry; Chemical processes; Circuits; Coils; Conductors; Industrial accidents; Industrial power systems; Manufacturing industries; Manufacturing processes; Power system reliability;
  • fLanguage
    English
  • Journal_Title
    Industry and General Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-943X
  • Type

    jour

  • DOI
    10.1109/TIGA.1966.4180636
  • Filename
    4180636