    Performance of the Pramod Johns scheme for UHS protection of EHV transmission lines under arcing fault conditions

  • Author

    Agrawal, Pramod

  • Author_Institution
    Power Syst. Consultants, London, UK
  • Volume
    6
  • Issue
    1
  • fYear
    1991
  • fDate
    1/1/1991 12:00:00 AM
  • Firstpage
    127
  • Lastpage
    134
  • Abstract
    The performance of the scheme of Pramod Agrawal (1989) for ultra-high-speed (UHS) protection of EHV transmission lines under arcing fault conditions is described. The arc with reignition effect is modeled, and a method for digital simulation of the superimposed arc voltage is discussed. Simulated tests have shown that the arc voltage has significant higher-frequency components. These tests also confirm that the arcing fault response repeats every half-cycle for a fault inception angle of the voltage from 0 to 90°, which is a significant improvement over schemes based on traveling-wave phenomena which have been considered a failure for faults at 0°C fault inception
  • Keywords
    arcs (electric); electrical faults; protection; transmission lines; EHV transmission lines; Pramod Johns scheme; UHS protection; arc voltage; arcing fault conditions; digital simulation; fault inception angle; reignition effect; ultra-high-speed protection; Circuit faults; Frequency; Power system protection; Power system transients; Power transmission lines; Switches; Transmission lines; Tuned circuits; Tuners; Voltage;