DocumentCode :
831360
Title :
Coordination of Fused Low-Voltage Distribution Systems
Author :
Smith, Martin
Author_Institution :
Bussmann Nanufacturing Division, McGraw-Edison Company
Issue :
5
fYear :
1967
Firstpage :
433
Lastpage :
437
Abstract :
The blowing of a fuse involves two distinct functions-that of melting the fusible element, and then extinguishing the arc that is formed. The development of the coordinated system, that is, one in which only the fuse closest to the fault will open, is obtained if the sum of the melting and arcing energy of the smaller fuse is less than the energy necessary to melt the larger fuse.
Keywords :
Art; Circuit faults; Current limiters; Fault currents; Fuses; Industrial power systems; Metals industry; Power generation economics; Power system protection; Voltage;