DocumentCode :
836304
Title :
Millisecond Zero Line Current and Large Line Current Phase Shifts from SCR Switching of Three-Phase Voltage Sources
Author :
Allen, George W.
Author_Institution :
Systems Development Division, IBM Corporation
Issue :
4
fYear :
1971
fDate :
7/1/1971 12:00:00 AM
Firstpage :
518
Lastpage :
524
Abstract :
Three-step switching by SCR at the line current zero points between different three-phase voltage sources causes significant line current phase shifts during the switching process, even for balanced resistive loads. It also causes a period of no current flow on one of the three-phase lines during the switching process. The phase shifts caused and the duration of the no current flow period is developed for various voltage ratios for balanced resistive loads. Extension of the results to reactive loads is addressed.
Keywords :
Commutation; Electronic equipment; Electronic equipment testing; Fires; Signal processing; Static power converters; Steady-state; Thyristors; Transactions Committee; Zero voltage switching;
fLanguage :
English
Journal_Title :
Industry and General Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-943X
Type :
jour
DOI :
10.1109/TIGA.1971.4181334
Filename :
4181334
Link To Document :
بازگشت