Title :
Maximum Frequency Decay Rate for Reactor Coolant Pump Motors
Author :
Hahn, R.S. ; Dasgupta, S. ; Baytch, E.M. ; Willoughby, R.D.
Author_Institution :
Boston Edison Company Boston, Massachusetts 02110
Abstract :
This paper presents methods and results of an analysis to determine the maximum expected frequency decay rate (FDR) at Pilgrim Station Unit 2, a nuclear power generating station utilizing a pressurized water reactor design. The maximum expected FDR would be of concern if it was greater than the FDR analogous to the freewheeling coast-down rate of the reactor coolant pump motors. This paper should benefit utilities and regulatory agencies evaluating pressurized water reactor station designs as it describes how to analyze the off-site power system. The paper includes discussions of the criteria for analytically creating overloads to force frequency excursions, load shedding and under-frequency relay effects on the FDR´s, important assumptions made, a comparison of FDR´s using different load models, and a comparison of the findings with those of other investigators.
Keywords :
Combustion; Coolants; Frequency; Inductors; Power generation; Power system modeling; Power system protection; Power system relaying; Power system transients; Voltage;
Journal_Title :
Nuclear Science, IEEE Transactions on
DOI :
10.1109/TNS.1979.4329739