Title :
13 Years´ Experience with Single-Phase Reclosing at 345 KV
Author_Institution :
Alcan Smelters and Chemicals Ltd
fDate :
3/1/1978 12:00:00 AM
Abstract :
Description is given of the Quebec power system of Alcan Smelters and Chemicals Ltd, with particular reference to two 345 kV transmission lines equipped with single-phase automatic reclosing and transfer trip. Performance of the reclosing feature over a 13- year period is reported and evaluated. Influence of counterpoise and overhead shield wires on reclosing and on lightning performance is discussed. Results indicate that the single-phase reclosing is successful in maintaining system stability, with either or both lines in operation.
Keywords :
Chemicals; Circuit breakers; Circuit faults; Lightning; Power system interconnection; Power system stability; Power transmission lines; Smelting; Steel; Wires;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1978.354513