DocumentCode
838244
Title
Operating Experience with Modulation of the Pacific HVDC Intertie
Author
Cresap, R.L. ; Mittelstadt, W.A. ; Scott, N. ; Taylor, C.W.
Author_Institution
Bonneville Power Administration
Issue
4
fYear
1978
fDate
7/1/1978 12:00:00 AM
Firstpage
1053
Lastpage
1059
Abstract
Implementation and operating experience with a control system which modulates power on the Pacific HVDC Intertie to damp oscillations on the parallel Pacific AC Intertie is described. This system significantly improves the damping of the Western interconnected power system, which has had a long history of periods of negatively damped oscillations. The successful operation of dc modulation was a key factor in permitting an increase in the rating of the Pacific AC Intertie from 2100 MW to 2500 MW. This uprating results in large economic and energy conservation benefits.
Keywords
Control systems; Damping; Frequency synchronization; HVDC transmission; History; Power generation economics; Power system economics; Power systems; Regulators; Transfer functions;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1978.354584
Filename
4181531
Link To Document