DocumentCode
838281
Title
Leader Propagation Model for Predetermination of Switching Surge Flashover Voltage of Large Air Gaps
Author
Hutzler, B. ; Hutzler-Barre, D.
Author_Institution
Electricite de France-Paris Direction des Etudes et Recherches
Issue
4
fYear
1978
fDate
7/1/1978 12:00:00 AM
Firstpage
1087
Lastpage
1096
Abstract
The breakdown voltage of an air gap submitted to switching surges may be predetermined by use of a mathematical model of leader propagation. This model is applied, in this article, to point plane gaps, for which a number of experimental results are available. It is possible to similate the development of a flashover: current, speed, visual appearence. U50 voltage and standard deviation may be deduced by simulation of test sequences and, as a result, the variations of these parameters, when the length of the gap and the shape of the applied wave vary, may be studied. Generally, results are found to be in accordance with experiments.
Keywords
Air gaps; Breakdown voltage; Corona; Electric breakdown; Flashover; Lightning; Power transmission lines; Shape; Surges; Testing;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1978.354588
Filename
4181535
Link To Document