Title :
Synthetic Methods for Testing of Vacuum Breakers
Author_Institution :
General Electric Company
fDate :
7/1/1978 12:00:00 AM
Abstract :
Different synthetic methods are scrutinized as to the applicability to vacuum breakers. Skeats method with resistor is brought forward and discussed from the viewpoint of breaker failure modes, interruption and circuit phenomena. Criteria for choice of resistor are given. Comparison tests using this method and direct method were performed. The results support theoretical conclusions by experimental verification of equivalency for the tested vacuum breaker. The method offers practical and economical advantages over current injection and is also suitable for multiloop and duty cycle testing.
Keywords :
Circuit breakers; Circuit simulation; Circuit testing; Electric breakdown; Knowledge engineering; Performance evaluation; Physics; Resistors; Vacuum arcs; Voltage;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1978.354618