• DocumentCode
    838690
  • Title

    Compensation Scheme for Single-Pole Switching on Untransposed Transmission Lines

  • Author

    Fakheri, A. ; Ware, B.J. ; Shperling, B.R.

  • Author_Institution
    AMERICAN ELECTRIC POWER
  • Issue
    4
  • fYear
    1978
  • fDate
    7/1/1978 12:00:00 AM
  • Firstpage
    1421
  • Lastpage
    1429
  • Abstract
    A Modified Four-Legged Reactor Scheme was developed for high speed, single-pole reclosing on untransposed lines. The new scheme, together with the simple four-legged reactor bank, effectively reduces the secondary arc current and the recovery voltage. Equations were derived to determine optimum neutral reactor values. Efficiency of the compensation scheme and the optimization procedure were verified by an example. The modified four-legged reactor bank includes four switches whose operations are coordinated with the line breakers. Switch parameters and suggestions for neutral reactor protection are given.
  • Keywords
    Admittance; Capacitance; Inductors; Power transmission lines; Protection; Switches; Symmetric matrices; Transmission line matrix methods; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1978.354628
  • Filename
    4181575