DocumentCode
839268
Title
Thermal Brealdown and Thermal Runaway Phenomena in EHV Cables
Author
Fukagawa, Hiromasa ; Imajo, Takahisa ; Sakamoto, Yukichi
Author_Institution
Central Research Institute of Electric Power Industry
Issue
5
fYear
1978
Firstpage
1885
Lastpage
1892
Abstract
The paper describes a new method of estimating thermal breakdown in EHV oil-impregnated paper-insulated cables with some experimental data. In the analysis it is shown with the computed results that the heat generation in the insulation can be exactly approximated by the average temperature of the insulation. In addition this method can calculate the critical voltage at which EHV cables go into thermal breakdown. The values here calculated compare agreeably with the breakdown voltages of 500 kV OF cables.
Keywords
Breakdown voltage; Cable insulation; Conductors; Data analysis; Dielectric losses; Dielectrics and electrical insulation; Electric breakdown; Oil insulation; Soil; Temperature;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1978.354684