Title :
Torsional Fatigue of Turbine-Generator Shafts Caused by Different Electrical System Faults and Switching Operations
Author :
Joyce, John S. ; Kulig, Tadeusz ; Lambrecht, Dietrich
Author_Institution :
Allis-Chalmers Power Systems, Inc.
Abstract :
The torsional stresses that occur in large steam turbine- generator shafts due to both planned and unplanned system switching operations are discussed. These operations include routine line switching, reclosing line-to-ground faults by either triple-pole or single-pole breaker operation, reclosing line-to-line and three-phase faults, malsynchronization and load rejection. The calculation of cumulative fatigue of individual turbine-generator shafts from computer-plotted torsional swing traces is explained. The benefits of single-pole breaker operation and of dividing the output of large generators between different electrical systems are briefly mentioned.
Keywords :
Circuit faults; Fatigue; Machinery; Power system faults; Power system transients; Senior members; Shafts; Stress; Transient analysis; Voltage;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :