Development of ±400 KV/±High and Medium-Pressure Oil-Filled Paper Insulated DC Power Cable System
Author :
Bahder, G. ; Eager, G.S., Jr. ; Seman, G.W. ; Fischer, F.E. ; Chu, H.
Author_Institution :
General Cable Corporation
Issue :
6
fYear :
1978
Firstpage :
2045
Lastpage :
2056
Abstract :
This paper describes the steps to be taken to optimize the design of oil-paper insulated power cable for high voltage dc operation. Experimental data is presented on models to establish the steady-state dc dielectric strength and the switching surge polarity reversal dielectric strength of oil-paper insulations. Laboratory data is presented on factory made prototype cables tested under voltage stress conditions applicable to a ±600 kV dc system. Optimized designs of high-pressure oil-filled pipe-type and medium-pressure oil-filled self-contained cables are presented.
Keywords :
Cable insulation; Design optimization; Dielectric breakdown; Dielectrics and electrical insulation; Oil insulation; Power cables; Power system modeling; Steady-state; Surges; Voltage;