DocumentCode :
839564
Title :
Air Humidity: An Important Factor for UHV Design
Author :
Büsch, W.
Author_Institution :
Electricity de France UHV Laboratory at Renardieres
Issue :
6
fYear :
1978
Firstpage :
2086
Lastpage :
2093
Abstract :
The switching-surge performance of long air gaps has been studied with regard to humidity. It has been found that humidity affects the flashover characteristics more than what could be expected from the present knowledge for large gap spacings . Based on physical observations of the discharge development, it has been shown that the position of the minimum of the U-curve changes: the minimum flashover voltage increases while the critical time-to-crest decreases with humidity. This results in important consequences for UHV insulation design.
Keywords :
Air gaps; Breakdown voltage; Circuit testing; Electric breakdown; Europe; Flashover; Humidity; IEC standards; Insulation testing; Laboratories;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1978.354712