• DocumentCode
    839872
  • Title

    Calculation of Current Transformer Transient Errors

  • Author

    Wiszniewski, A.

  • Author_Institution
    Faculty of Engineering, University of Gar-Younis
  • Issue
    6
  • fYear
    1978
  • Firstpage
    2339
  • Lastpage
    2345
  • Abstract
    Transient saturation of current transformers may cause maloperation of protective devices. Therefore there is a need for a method which enables the calculating of transient transformation errors. The method should be simple and based upon the data which are available to the users of current transformers. The method presented adopts the first harmonic approach and uses simplifications which result from experimental study of many oscillograms of current transformers transient states. The simple equations make it possible to calculate aperiodic and first harmonic components of magnetizing and secondary currents in the transient states which involve saturation. The transient errors related to the transformation of the first harmonic may be easily determined, together with the time intervals in which they exceed given limits. Correlation between the method and the full digital model of a current transformer is satisfactory.
  • Keywords
    Circuit faults; Current transformers; Equations; Error correction; Power system harmonics; Power system relaying; Power system transients; Protection; Protective relaying; Saturation magnetization;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1978.354739
  • Filename
    4181688