DocumentCode :
839872
Title :
Calculation of Current Transformer Transient Errors
Author :
Wiszniewski, A.
Author_Institution :
Faculty of Engineering, University of Gar-Younis
Issue :
6
fYear :
1978
Firstpage :
2339
Lastpage :
2345
Abstract :
Transient saturation of current transformers may cause maloperation of protective devices. Therefore there is a need for a method which enables the calculating of transient transformation errors. The method should be simple and based upon the data which are available to the users of current transformers. The method presented adopts the first harmonic approach and uses simplifications which result from experimental study of many oscillograms of current transformers transient states. The simple equations make it possible to calculate aperiodic and first harmonic components of magnetizing and secondary currents in the transient states which involve saturation. The transient errors related to the transformation of the first harmonic may be easily determined, together with the time intervals in which they exceed given limits. Correlation between the method and the full digital model of a current transformer is satisfactory.
Keywords :
Circuit faults; Current transformers; Equations; Error correction; Power system harmonics; Power system relaying; Power system transients; Protection; Protective relaying; Saturation magnetization;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1978.354739