    Field test of 275-kV internally water cooled XLPE cable system

  • Author

    Ogawa, Katsunori ; Kurata, Mamoru ; Suzuki, Hiroshi ; Kawasaki, Katsutoshi ; Imai, Noriaki ; Nakamura, Shigehito ; Sakai, Seiichiro

  • Author_Institution
    Tokyo Electr. Power Co. Inc., Japan
  • Volume
    4
  • Issue
    1
  • fYear
    1989
  • fDate
    1/1/1989 12:00:00 AM
  • Firstpage
    8
  • Lastpage
    18
  • Abstract
    A 275 kV internally-water-cooled XLPE power cable with a stainless steel coolant tube and a wire shield was developed that greatly reduced the consumption of ion exchange resins and the sheath eddy current loss, respectively. A 230 m cable system which included the cable, cable accessories and cooling facilities was constructed, and a field test was carried out over a two year period. The long-term stability and reliability of the cable system were confirmed by the field test and a subsequent residual performance test. The practicality of the cable system was further ensured by developing novel methods of system recovery from faults
  • Keywords
    cable insulation; cable testing; power cables; 275 kV; XLPE power cable; cooling; field test; ion exchange resins; performance; polymers; reliability; sheath eddy current loss; stability; Cable shielding; Coolants; Cooling; Eddy currents; Power cables; Resins; Stability; Steel; System testing; Wire;