DocumentCode :
843052
Title :
Measured data transmission performance for AM broadcast-VHF radio distribution automation communication system
Author :
Anderson, Harry R.
Author_Institution :
H.R. Anderson & Associates Inc., Eugene, OR, USA
Volume :
4
Issue :
1
fYear :
1989
fDate :
1/1/1989 12:00:00 AM
Firstpage :
82
Lastpage :
89
Abstract :
The measured data transmission signaling performance for an AM broadcast (outbound) VHF radio (inbound) two-way distribution automation system is presented. The performance data are presented as a function of signal level, transmission path length and time of day. The outbound link, which uses inaudible low-speed phase modulation of the carrier of a standard AM broadcast station, demonstrated overall average signaling success rates of better than 99% in operational transceiver units. For the 154 MHz VHF return link, which used unconventional low-speed amplitude modulation resolved by a real-time FFT detector-receiver, the measured overall signaling success rate averaged about 60%
Keywords :
distribution networks; power system computer control; radio systems; telecontrol equipment; 154 MHz; AM broadcast; VHF radio; amplitude modulation; distribution automation; phase modulation; power system telecontrol; radio systems; signal level; signaling performance; transceiver units; transmission path length; Amplitude modulation; Automatic control; Automation; Communication system control; Control systems; Data communication; Phase modulation; Radio broadcasting; System testing; Transceivers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.19191
Filename :
19191
Link To Document :
بازگشت