DocumentCode
843083
Title
Mutual coupling between finite lengths of parallel or angled horizontal earth return conductors
Author
Rogers, Eldon J. ; White, John F.
Author_Institution
Bonneville Power Adm., Vancouver, WA, USA
Volume
4
Issue
1
fYear
1989
Firstpage
103
Lastpage
113
Abstract
Mutual coupling between earth return current and potential test conductors used during stage tests of a grounding system is discussed. The coupling is a source of significant error in measuring grounding potential and grounding system impedance. Mutual impedance formulae are presented for correcting mutual coupling errors resulting from any length of paralleled or angled horizontal ground return current and potential conductors. The formulae are an extension of the complex image plane approximation of J.R. Carson´s (1926) formula for infinitely long parallel conductors.<>
Keywords
earthing; power system measurement; power system protection; complex image plane approximation; earth return conductors; grounding system; impedance; mutual coupling; potential test; power system measurement; power system protection; Conductors; Current measurement; Earth; Equations; Frequency; Grounding; Impedance; Mutual coupling; Power engineering and energy; System testing;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.19196