DocumentCode :
845042
Title :
Investigation of interruption performance of newly developed 300 kV 3-phase-in-one-tank-type GCB and its application to a reduced size GIS
Author :
Suzuki, K. ; Ikeda, H. ; Mizoguchi, H. ; Ozaki, Y. ; Yanabu, S.
Author_Institution :
Toshiba Corp., Kawasaki, Japan
Volume :
4
Issue :
1
fYear :
1989
fDate :
1/1/1989 12:00:00 AM
Firstpage :
362
Lastpage :
367
Abstract :
With the objective of diminishing the distance between bays of SF 6 gas insulated switchgear (GIS), a 300 kV three-phase-in-one-tank-type gas circuit breaker (GCB) has been developed. The size of the interrupting chamber has been reduced to decrease the diameter of the GCB tank. Hot gas flow has been optimized analytically and the deterioration of insulation performance caused by the hot gas between the poles has been investigated. A more compact GIS with fewer parts and easier to install results from the study
Keywords :
gas blast circuit breakers; gaseous insulation; sulphur compounds; 3-phase-in-one-tank-type GCB; 300 kV; SF6 gas insulated switchgear; gas-blast circuit breakers; hot gas flow; insulation performance; interruption performance; Circuit breakers; Current transformers; Fluid flow; Gas insulation; Geographic Information Systems; Senior members; Substations; Sulfur hexafluoride; Switchgear; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.19225
Filename :
19225
Link To Document :
بازگشت