• DocumentCode
    845999
  • Title

    The lightning performance of unshielded steel-structure transmission lines

  • Author

    Mousa, Abdul M. ; Srivastava, K.D.

  • Author_Institution
    British Columbia Hydro, Vancouver, BC, Canada
  • Volume
    4
  • Issue
    1
  • fYear
    1989
  • fDate
    1/1/1989 12:00:00 AM
  • Firstpage
    437
  • Lastpage
    445
  • Abstract
    A method is presented for calculating the lightning performance of unshielded steel-structure transmission lines. The method is an adaptation of the Anderson/IEEE method for shielded lines, and it incorporates an algorithm for calculating separate magnitudes and frequency distributions of the strokes to the towers and the strokes to the conductors. The results of applying the method to 230 kV, 500 kV and 765 kV lines are presented, and the effects of voltage class, span and form of striking distance equation are discussed
  • Keywords
    lightning protection; poles and towers; power overhead lines; transmission networks; 230 kV; 500 kV; 765 kV; Anderson/IEEE method; lightning performance; striking distance; towers; unshielded steel-structure transmission lines; Circuits; Flashover; Frequency; Insulation; Lightning; Poles and towers; Power transmission lines; Transmission lines; Voltage; Wires;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.19234
  • Filename
    19234