• DocumentCode
    847336
  • Title

    Staged fault and laboratory tests on a cable pair protection system designed to serve power stations

  • Author

    Geer, Eugene W., Jr. ; Whatmough, J.R.

  • Author_Institution
    Bell Laboratories, Whippany, N. J.
  • Volume
    94
  • Issue
    1
  • fYear
    1975
  • Firstpage
    51
  • Lastpage
    57
  • Abstract
    Cable pairs entering power stations may be subjected to ground potential rise (GPR) and/or induction of several thousand volts during power system faults. A cable protection system designed to give a high degree of reliability is described, and the results of staged fault and laboratory tests are discussed. An analysis of neutralizing transformer transient performance shows how the transformer´s behavior during fault conditions is determined by its volt-time capability.
  • Keywords
    Ground penetrating radar; Laboratories; Performance analysis; Power cables; Power generation; Power system faults; Power system protection; Power system reliability; Power system transients; System testing;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1975.31824
  • Filename