DocumentCode
847336
Title
Staged fault and laboratory tests on a cable pair protection system designed to serve power stations
Author
Geer, Eugene W., Jr. ; Whatmough, J.R.
Author_Institution
Bell Laboratories, Whippany, N. J.
Volume
94
Issue
1
fYear
1975
Firstpage
51
Lastpage
57
Abstract
Cable pairs entering power stations may be subjected to ground potential rise (GPR) and/or induction of several thousand volts during power system faults. A cable protection system designed to give a high degree of reliability is described, and the results of staged fault and laboratory tests are discussed. An analysis of neutralizing transformer transient performance shows how the transformer´s behavior during fault conditions is determined by its volt-time capability.
Keywords
Ground penetrating radar; Laboratories; Performance analysis; Power cables; Power generation; Power system faults; Power system protection; Power system reliability; Power system transients; System testing;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1975.31824
Filename
1601426
Link To Document