Energization of large shunt reactors near static VAR compensators and HVDC converters
Author :
Puente, H.R. ; Burgess, M.L. ; Larsen, E.V. ; Elahi, H.
Author_Institution :
El Paso Electr. Co., TX, USA
Volume :
4
Issue :
1
fYear :
1989
fDate :
1/1/1989 12:00:00 AM
Firstpage :
629
Lastpage :
636
Abstract :
A case study is presented involving the switching of large reactors on a power transmission system including an HVDC terminal and static VAR compensator in close proximity. Switching the subject reactor without preinsertion resistors led to field problems with harmonic distortion and offset currents. The study provides insight to the system behavior for reactor switching events. The results provide a sound basis for selecting control and equipment modifications to permit normal reactor switching
Keywords :
harmonics; power convertors; reactors (electric); static VAr compensators; HVDC converters; harmonic distortion; offset currents; shunt reactors; static VAR compensators; Circuit faults; HVDC transmission; Harmonic distortion; Inductors; Resistors; Shunt (electrical); Static VAr compensators; Substations; Switches; Voltage;