DocumentCode :
847528
Title :
Dynamic measurements during short-circuit testing of transformers part II: Test results and analysis
Author :
Ayers, R.E. ; Usry, G.O. ; Patel, M.R. ; Steel, R.B.
Author_Institution :
General Electric Company, Rome, Georgia
Volume :
94
Issue :
2
fYear :
1975
fDate :
3/1/1975 12:00:00 AM
Firstpage :
198
Lastpage :
206
Abstract :
Some of the test results measured during short circuit tests on a full size, 19.5 MVA, three phase, three winding, oil filled, power transformer are reported and analyzed in this paper. Included are radial flux measurements to obtain accurate calculated electromagnetic forces, the effects of tap configuration and clamping force on the dynamic forces transmitted to various parts of the transformer structure, comparison of the measured results with computer predicted results, the circumferential force variation at the top of the winding, the forces experienced by the tie plates, and the failure detection results.
Keywords :
Circuit testing; Clamps; Electromagnetic forces; Electromagnetic measurements; Force measurement; Petroleum; Phase measurement; Power measurement; Power transformers; Size measurement;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1975.31842