DocumentCode
847834
Title
Prediction of electromagnetic field and current transients in power transmission and distribution systems
Author
Thomas, D.E. ; Wiggins, C.M. ; Nickel, F.S. ; Ko, C.D. ; Wright, S.E.
Author_Institution
BDM Corp., Albuquerque, NM, USA
Volume
4
Issue
1
fYear
1989
fDate
1/1/1989 12:00:00 AM
Firstpage
744
Lastpage
755
Abstract
A time-domain model is described for predicting transient bus currents, electromagnetic fields, and cable-coupling effects caused by switching actions in high-voltage substations. Having been validated against measured transient data, the model provides a basis for predicting EMI effects resulting from abnormal switching actions, such as phase-to-ground faults, which are difficult to stage for measurement. From such worst-case estimates, the adequacy of the latest standards for microprocessor-controlled substation protection can be assessed
Keywords
distribution networks; electromagnetic interference; switching substations; transients; transmission network calculations; EM field transients; EMI effects; abnormal switching actions; cable-coupling effects; current transients; distribution systems; high-voltage substations; microprocessor-controlled substation protection; phase-to-ground faults; power transmission systems; time-domain model; transient bus currents; Electromagnetic coupling; Electromagnetic fields; Electromagnetic modeling; Electromagnetic transients; Power cables; Power system transients; Power transmission; Predictive models; Substations; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.19267
Filename
19267