• DocumentCode
    847931
  • Title

    UHV tower insulation parameters determined by full-scale testing

  • Author

    Pokorny, W.C. ; Flugum, R.W.

  • Author_Institution
    American Electric Power Service Corp., New York, N.Y
  • Volume
    94
  • Issue
    2
  • fYear
    1975
  • fDate
    3/1/1975 12:00:00 AM
  • Firstpage
    518
  • Lastpage
    529
  • Abstract
    A comprehensive series of impulse tests on a variety of simulated UHV tower windows is described in this paper. The tests overlap and extend existing data, making available switching surge flashover characteristics of tower windows up to 37 meters in width. All of the raw test data is included for comparison with similar programs in other laboratories. The effects of several variables on statistically derived flashover voltages are described, and application data for tower insulation up to 1900-kV transmission levels is derived from the test data.
  • Keywords
    Conductors; Flashover; Impulse testing; Insulation testing; Poles and towers; Probability; Shape; Surges; Test equipment; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1975.31879
  • Filename
    1601481