• DocumentCode
    847961
  • Title

    Switching-surge flashover characteristics of long sphere-plane gaps for UHV station design

  • Author

    Schneider, H.M. ; Turner, F.J.

  • Author_Institution
    General Electric Company, Pittsfield, Massachusetts
  • Volume
    94
  • Issue
    2
  • fYear
    1975
  • fDate
    3/1/1975 12:00:00 AM
  • Firstpage
    551
  • Lastpage
    560
  • Abstract
    The switching-surge behavior of UHV station electrodes was studied by investigating the performance of sphere-plane gaps. Design curves which show the effect of electrode curvature on the critical flashover voltage for spheres ranging in diameter from 0.5 to 2.5 meters and with gap spacings between 1 and 11 meters are presented. The influence of waveshape on large electrode flashover characteristics was obtained by varying the time-to-crest of the applied waveforms between 75 and 1220 µs. Test data are given for smooth and segmented spheres during dry conditions. The effect of precipitation on the switchlng-surge strength was investigated by wetting the sphere surfaces either by natural rain or artificial means. The results presented provide information required for the switchlng-surge design of outdoor UHV stations.
  • Keywords
    AC generators; Corona; Electrodes; Flashover; Insulation; Poles and towers; Shape; Surges; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1975.31883
  • Filename