DocumentCode
847961
Title
Switching-surge flashover characteristics of long sphere-plane gaps for UHV station design
Author
Schneider, H.M. ; Turner, F.J.
Author_Institution
General Electric Company, Pittsfield, Massachusetts
Volume
94
Issue
2
fYear
1975
fDate
3/1/1975 12:00:00 AM
Firstpage
551
Lastpage
560
Abstract
The switching-surge behavior of UHV station electrodes was studied by investigating the performance of sphere-plane gaps. Design curves which show the effect of electrode curvature on the critical flashover voltage for spheres ranging in diameter from 0.5 to 2.5 meters and with gap spacings between 1 and 11 meters are presented. The influence of waveshape on large electrode flashover characteristics was obtained by varying the time-to-crest of the applied waveforms between 75 and 1220 µs. Test data are given for smooth and segmented spheres during dry conditions. The effect of precipitation on the switchlng-surge strength was investigated by wetting the sphere surfaces either by natural rain or artificial means. The results presented provide information required for the switchlng-surge design of outdoor UHV stations.
Keywords
AC generators; Corona; Electrodes; Flashover; Insulation; Poles and towers; Shape; Surges; Testing; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1975.31883
Filename
1601485