Measurement of harmonic currents and evaluation of the DC filter performance of the New England-Hydro-Quebec Phase I HVDC project
Author :
Garrity, T.F. ; Hassan, I.D. ; Adamson, K.A. ; Donahue, J.A.
Author_Institution :
Ebasco Services Inc., New York, NY, USA
Volume :
4
Issue :
1
fYear :
1989
fDate :
1/1/1989 12:00:00 AM
Firstpage :
779
Lastpage :
786
Abstract :
Measurements were conducted to determine the cause of increased telephone interference and to evaluate the DC filter performance. The measurements revealed unexpected high levels of three-pulse harmonic currents in the DC pole conductors. The cause is attributed to imbalances within the six-pulse bridges caused by the converter transformer and valve stray capacitances to ground. The conventional model of the converter power circuit used as the basis for the DC filter design does not reproduce the measured three-pulse harmonics
Keywords :
DC power transmission; filters; harmonics; power system interconnection; power system measurement; 450 kV; 690 MW; DC filter performance; DC pole conductors; HVDC; New England-Hydro-Quebec intertie; Phase I project; converter transformer; harmonic currents; six-pulse bridges; telephone interference; three-pulse harmonic currents; valve stray capacitances to ground; Bridge circuits; Capacitance; Conductors; Current measurement; Interference; Power harmonic filters; Power measurement; Power system harmonics; Telephony; Valves;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.19270
Filename :
19270
Link To Document :
بازگشت