DocumentCode
848444
Title
A half cycle static bus protection relay using instantaneous voltage measurement
Author
Mentler, Sandor
Author_Institution
General Electric Co., Philadelphia, Pa.
Volume
94
Issue
3
fYear
1975
fDate
5/1/1975 12:00:00 AM
Firstpage
939
Lastpage
944
Abstract
A high impedance bus protection relay using thyristors and based on instantaneous voltage measurement is described. Half-cycle operating speed is achieved and power dissipation is minimized. Application is no longer limited by the kneepoint of the C.T. excitation characteristic and peak C.T. secondary voltages are accurately limited, regardless of fault magnitude.
Keywords
Circuit faults; Equations; Fault currents; Protection; Protective relaying; Relays; Resistors; Solid state circuits; Switches; Voltage measurement;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1975.31926