  • Abstract
    A high impedance bus protection relay using thyristors and based on instantaneous voltage measurement is described. Half-cycle operating speed is achieved and power dissipation is minimized. Application is no longer limited by the kneepoint of the C.T. excitation characteristic and peak C.T. secondary voltages are accurately limited, regardless of fault magnitude.
  • Keywords
    Circuit faults; Equations; Fault currents; Protection; Protective relaying; Relays; Resistors; Solid state circuits; Switches; Voltage measurement;