DocumentCode :
849363
Title :
Mechanical effects of high short-circuit currents in substations
Author :
Landin, J.I. ; Lindqvist, C.I. ; Bergstrom, L.R. ; Cullen, G.R.
Author_Institution :
Swedish State Power Board, Stockholm, Sweden
Volume :
94
Issue :
5
fYear :
1975
Firstpage :
1657
Lastpage :
1665
Abstract :
Tests have been made of the short-circuit stresses on 145 kV busbar systems with flexible conductors. The influence of different parameters has been studied such as span length, sag, conductor type, conductor spacing, spring effect in towers etc. Currents of 20-50 kArmsand short-circuit times 0,1-0,5 s have been studied. The results have been compared with results from manual and computer calculations.
Keywords :
Conductors; Electromagnetic measurements; Frequency; Insulation; Poles and towers; Springs; Strain measurement; Stress; Substations; Testing;
fLanguage :
English