DocumentCode :
849420
Title :
Prevention of high-fault rupture of pole-type distribution transformers
Author :
Mahieu, W.R.
Author_Institution :
A. B. Chance Company, Centralia, Mo.
Volume :
94
Issue :
5
fYear :
1975
Firstpage :
1698
Lastpage :
1707
Abstract :
Violent rupture of distribution transformers has occurred with increasing frequency in recent years. The problem appears greatest with pole-type units at locations with high available short-circuit currents. This paper concerns the rupture of pole-type distribution transformers subjected to internal, submerged, arcing faults of high current magnitude. An analysis of a probable rupture process and tests of faulted transformers were used to obtain a simple semi-empirical equation for the internal transformer pressure rise. Limiting the I2t during the fault with current limiting fuses is shown to be a practical means of minimizing the probability of transformer rupture.
Keywords :
Algorithm design and analysis; Current limiters; Equations; Fault currents; Frequency; Fuses; Petroleum; Physics computing; Testing; Transformers;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1975.32013
Filename :
1601615
Link To Document :
بازگشت