Title :
Overvoltages with remotely-switched cable-fed grounded wye-wye transformers
Author :
Smith, D.R. ; Swanson, S.R. ; Borst, J.D.
Author_Institution :
Westinghouse Electric Corporation, East Pittsburgh, Pennsylvania
Abstract :
The system and transformer characteristics which can result in overvoltages and ferroresonance when energizing grounded-wye/ grounded-wye distribution transformers from a remote location with single-pole switches are defined. A qualitative analysis of a system typical of those installed today is presented to show how the overvoltages can occur during single-pole switching. Full-scale laboratory tests were conducted to determine maximum overvoltages and obtain a better understanding of the phenomenon. The results show that distinct responses occur during the single-pole energization, and ferroresonance can occur contrary to statements appearing in many references.
Keywords :
Cable shielding; Capacitance; Coupling circuits; Hydrogen; Impedance; Magnetic cores; Surges; Switches; Switching circuits; Transformer cores;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/T-PAS.1975.32030