DocumentCode
849597
Title
Overvoltages with remotely-switched cable-fed grounded wye-wye transformers
Author
Smith, D.R. ; Swanson, S.R. ; Borst, J.D.
Author_Institution
Westinghouse Electric Corporation, East Pittsburgh, Pennsylvania
Volume
94
Issue
5
fYear
1975
Firstpage
1843
Lastpage
1853
Abstract
The system and transformer characteristics which can result in overvoltages and ferroresonance when energizing grounded-wye/ grounded-wye distribution transformers from a remote location with single-pole switches are defined. A qualitative analysis of a system typical of those installed today is presented to show how the overvoltages can occur during single-pole switching. Full-scale laboratory tests were conducted to determine maximum overvoltages and obtain a better understanding of the phenomenon. The results show that distinct responses occur during the single-pole energization, and ferroresonance can occur contrary to statements appearing in many references.
Keywords
Cable shielding; Capacitance; Coupling circuits; Hydrogen; Impedance; Magnetic cores; Surges; Switches; Switching circuits; Transformer cores;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1975.32030
Filename
1601632
Link To Document