  • Title

    Overvoltages with remotely-switched cable-fed grounded wye-wye transformers

  • Author

    Smith, D.R. ; Swanson, S.R. ; Borst, J.D.

  • Author_Institution
    Westinghouse Electric Corporation, East Pittsburgh, Pennsylvania
  • Volume
    94
  • Issue
    5
  • fYear
    1975
  • Firstpage
    1843
  • Lastpage
    1853
  • Abstract
    The system and transformer characteristics which can result in overvoltages and ferroresonance when energizing grounded-wye/ grounded-wye distribution transformers from a remote location with single-pole switches are defined. A qualitative analysis of a system typical of those installed today is presented to show how the overvoltages can occur during single-pole switching. Full-scale laboratory tests were conducted to determine maximum overvoltages and obtain a better understanding of the phenomenon. The results show that distinct responses occur during the single-pole energization, and ferroresonance can occur contrary to statements appearing in many references.