• DocumentCode
    849703
  • Title

    A field study of the short-line-fault component of transient recovery voltage

  • Author

    Colclaser, R.C., Jr. ; Beehler, J.E. ; Garrity, T.F.

  • Author_Institution
    University of Pittsburgh, Pittsburgh, Pa
  • Volume
    94
  • Issue
    6
  • fYear
    1975
  • Firstpage
    1943
  • Lastpage
    1953
  • Abstract
    The short-line-fault transient recovery voltage component is a critical factor in arc interruption. This paper is a study of 345kV field data, generated by a pulse test circuit, which develops inherent characteristics for the "bare" line. The modifying effects of terminal equipment on the shape of the saw-tooth component are demonstrated experimentally and theoretically. Test results are compared with present ANSI Standard requirements to verify the application.
  • Keywords
    Current measurement; Diodes; Inductors; Interrupters; Oscilloscopes; Poles and towers; Pulse transformers; Test equipment; Testing; Voltage;