DocumentCode
849703
Title
A field study of the short-line-fault component of transient recovery voltage
Author
Colclaser, R.C., Jr. ; Beehler, J.E. ; Garrity, T.F.
Author_Institution
University of Pittsburgh, Pittsburgh, Pa
Volume
94
Issue
6
fYear
1975
Firstpage
1943
Lastpage
1953
Abstract
The short-line-fault transient recovery voltage component is a critical factor in arc interruption. This paper is a study of 345kV field data, generated by a pulse test circuit, which develops inherent characteristics for the "bare" line. The modifying effects of terminal equipment on the shape of the saw-tooth component are demonstrated experimentally and theoretically. Test results are compared with present ANSI Standard requirements to verify the application.
Keywords
Current measurement; Diodes; Inductors; Interrupters; Oscilloscopes; Poles and towers; Pulse transformers; Test equipment; Testing; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1975.32040
Filename
1601642
Link To Document