• DocumentCode
    849733
  • Title

    A three-phase differential relay for transformer protection

  • Author

    Einvall, C.-H. ; Linders, J.R.

  • Author_Institution
    Asea, Vasteras, Sweden
  • Volume
    94
  • Issue
    6
  • fYear
    1975
  • Firstpage
    1971
  • Lastpage
    1980
  • Abstract
    Established harmonic restraint differential relay concepts have been enlarged upon to provide a new static multiple-winding transformer differential relay. The resulting design includes simplification of the frequency selective circuits and new techniques for rapidly determining the harmonic content of the applied currents. The relay is shown to have improved sensitivity, to be responsive to internal transformer winding faults in less than two cycles, and to the more severe type of fault in less than one cycle. Full security against inrush currents and overexcitation as well as to external faults is demonstrated. Poor performance of current transformers is shown not to adversely affect either the security or dependability of the relay. Heavy current test results are presented which confirm the relay principles.
  • Keywords
    Circuit faults; Current transformers; Frequency; Harmonic distortion; Power harmonic filters; Protection; Protective relaying; Relays; Security; Surges;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1975.32043
  • Filename
    1601645