DocumentCode :
850093
Title :
Real-time optimal power flow in automatic generation control
Author :
Bacher, Rainer ; Van Meeteren, Hans P.
Author_Institution :
Control Data Corp., Minneapolis, MN, USA
Volume :
3
Issue :
4
fYear :
1988
fDate :
11/1/1988 12:00:00 AM
Firstpage :
1518
Lastpage :
1529
Abstract :
The authors describe the concept, mathematical formulation, and solution of a real-time OPF (optimal power flow) in an energy management system. The real-time OPF replaces a classical real-time economic dispatch whenever a network flow violation occurs. To meet performance requirements (solution speed and frequency of execution) a two-stage approach is proposed. A full OPF is first executed in a nontime-critical mode and the critical branch flows are determined. Then, a constrained economic dispatch is executed based on the critical constraint set determined during the first stage. The execution frequency of the second stage is the same as the execution frequency of a standard real-time economic dispatch
Keywords :
load dispatching; load flow; load management; power system analysis computing; automatic generation control; constrained economic dispatch; energy management system; network flow violation; real-time optimal power flow; Automatic control; Automatic generation control; Costs; Frequency; Fuel economy; Load flow; Piecewise linear approximation; Power generation economics; Power system economics; Quadratic programming;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/59.192961
Filename :
192961
Link To Document :
بازگشت