• DocumentCode
    850228
  • Title

    Synthetic polymer papers suitable for use in EHV underground cable insulation

  • Author

    Fujita, H. ; Itoh, Hayato

  • Author_Institution
    Dainichi-Nippon Cables, Ltd., Amagasaki, Hyogo, Japan
  • Volume
    95
  • Issue
    1
  • fYear
    1976
  • Firstpage
    130
  • Lastpage
    139
  • Abstract
    This relates to the applicability of TenaxRpaper made of poly(2,6-diphenyl-p-phenylene oxide) fibers to EHV cable insulation. Tenax paper shows excellent thermal stability in DDB impregnant even at 150° and its impulse strength has been improved significantly. Long-term dielectric test on model cable suggests that Tenax paper insulation may provide an EHV cable capable of operating at 25 kV/mm and 120°. Some experimental 275 kV cables are manufactured and offer much valuable imformation. Additional calculation based on the data available indicates that Tenax paper insulated oil-filled cables rated at lOO0 KV may offer much power capability advantage.
  • Keywords
    Cable insulation; Dielectrics and electrical insulation; Insulation testing; Manufacturing; Oil filled cables; Oil insulation; Optical fiber cables; Optical fiber testing; Polymers; Thermal stability;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1976.32085
  • Filename
    1601687