DocumentCode :
850236
Title :
The effects of SF6- N2mixture upon the recovery voltage capability of a synchronous interrupter
Author :
Garzon, R.D.
Author_Institution :
I-T-E Imperial Corporation, Spring House, Penna
Volume :
95
Issue :
1
fYear :
1976
Firstpage :
140
Lastpage :
144
Abstract :
The experimental results showing the relation between rate of rise of recovery voltage (RRRV) and percentage of N2- SF6mixture, by pressure, are reported. A description of the test vehicle and the test procedure is also included. For a constant di/dt the optimum interrupter performance, judged in terms of its voltage recovery capability, is observed to occur when the SF6mixed with N2is in the range of 40 to 50 percent. In the limited range of pressures tested, the voltage recovery capability showed to be proportional to the upstream pressure raised to the 1.5 power.
Keywords :
Acceleration; Circuit breakers; Circuit testing; Dielectric breakdown; Gas insulation; Interrupters; Springs; Sulfur hexafluoride; Vehicles; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1976.32086
Filename :
1601688
Link To Document :
بازگشت