DocumentCode
850479
Title
Reactive power control by least squares minimization
Author
Shoults, Raymond R. ; Chen, Mo-Shing
Author_Institution
University Computing Company, Dallas, Texas
Volume
95
Issue
1
fYear
1976
Firstpage
325
Lastpage
334
Abstract
An effective method is presented for performing reactive power control in a bulk power supply system by optimally rescheduling generator terminal voltage magnitudes and/or transformer tap settings. The optimization procedure is the familar least squares minimization technique and is suitable for on-line application in energy control center computers. Sensitivity factors provide the basis for the control function and are developed from a linearized reactive power model. Important features of this method include a model approximating the reactive power flow through a load-tap-changing (LTC) transformer and a Norton´s equivalent circuit model approximating the reactive power output of a regulating generator. As a result of the linear models developed, optimally ordered triangular factorization is fully exploited to enhance computational speed and efficiency. Test results are presented to demonstrate the effectiveness of the method. A linearized active power model is briefly presented to illustrate its dual relationship to the linearized reactive power model. This is an important relationship, enabling both active and reactive power control by application of the same general model.
Keywords
Application software; Circuit testing; Equivalent circuits; Least squares approximation; Least squares methods; Minimization; Power generation; Power supplies; Reactive power; Reactive power control;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1976.32109
Filename
1601711
Link To Document